Quality & approvals

Tested before it leaves.

Certified management systems, routine testing on every unit, and every product mapped to the Indian Standard and its international equivalent.

Routine test panel

Routine test panel

01

Our position

Quality you can trace to a bay.

Owning the process from raw material to tested product means there is no vendor to point at.

Every transformer, conductor and cable is routine-tested before dispatch. Steel is inspected on receipt, coating thickness is checked after galvanizing, and extruded product is monitored continuously for wall thickness and dimension.

Purchasers and third-party agencies may witness testing, including pre-shipment inspection for export.

ISO9001
quality management systems · 9001:2015
ISO14001
environmental management · 14001:2015
ISO45001
occupational health and safety · 45001:2018
02

Standards

What we manufacture against.

Indian Standards and their international equivalents, so a domestic specification translates directly into an export one.

ProductIndian StandardInternational equivalent
Distribution transformersIS 1180 (Part 1):2014 Amd. 4 · IS 2026IEC 60076
Power transformersIS 2026 (Parts 1–5)IEC 60076
Solar / inverter duty transformersIS 2026 · IS 1180IEC 60076 · IEEE C57.110 · C57.159
Servo voltage stabilisersIS 9815 (Part 1)—
ACSR conductorIS 398 (Part 2):1996IEC 61089
LT & XLPE cableIS 7098 (Part 1) & (Part 2)IEC 60502-1
PCC polesIS 1678:1998 · IS 785:1998—
GalvanizingIS 4759:1996 · IS 2629:1985ISO 1461:2009
HDPE pipeIS 4984ISO 4427
Drip lateralIS 13488:2008 · IS 13487ISO 9261
Mini sprinklerIS 14605ISO 8026

“—”: no international equivalent in common use.

03

Testing

What happens before dispatch.

Routine testing is built into production, not bolted on at the end of it.

Transformers

Electrical routine tests

Ratio, polarity, vector group, winding resistance, losses at 50% and 100%, impedance, insulation and dielectric withstand.

Conductor & cable

Dimensional & electrical

Diameter, lay ratio, resistance, breaking load, insulation resistance and high voltage test.

Galvanized steel

Coating verification

Coating mass to IS 6745, uniformity to IS 2633 and adhesion to IS 2629 after the zinc bath.

Polymer

Extrusion control

Continuous wall thickness and outside diameter monitoring, plus hydrostatic pressure testing.

The laboratory

Where the numbers come from.

Routine test panel
Routine test panel
Test control desk
Test control desk
Quality control laboratory
Quality control laboratory
Sample preparation
Sample preparation
Cable testing
Cable testing
04

Certifications

Certificates and type tests.

Each certificate is issued against a specific product and rating. Numbers and validity dates are sent with the quotation, or on request.

CertificateScopeIssued byNumber · validity
ISO 9001:2015Quality management — manufacturing operationsOn enquiryOn enquiry
ISO 14001:2015Environmental managementOn enquiryOn enquiry
ISO 45001:2018Occupational health and safetyOn enquiryOn enquiry
BIS licence — IS 1180 (Part 1)Distribution transformersBureau of Indian StandardsCM/L number On enquiry
BEE star labelDistribution transformers, star level per modelBureau of Energy EfficiencyOn enquiry
Type tests — transformersShort-circuit, impulse and temperature rise, per ratingCPRI / ERDAReport numbers On enquiry
Type tests — conductor and cableMechanical and electrical, per sizeNABL-accredited laboratoryReport numbers On enquiry
Routine test certificateEvery transformer, conductor and cable before dispatchAggarwal Global worksAvailable on request

Fields marked On enquiry are issued against a specific enquiry.

05

For export buyers

IS against IEC

Indian temperature-rise limits are stricter than IEC 60076-2, so a transformer built to IS 1180 meets a tougher thermal standard.

Temperature rise limits — IS 1180 (Part 1) against IEC 60076-2
ClassWinding riseTop-oil riseAmbient
Three-phase up to 200 kVA (IS 1180)40 K35 K50 °C
Three-phase above 200 up to 2500 kVA (IS 1180)45 K40 K50 °C
Single-phase up to 25 kVA (IS 1180)40 K35 K50 °C
IEC 60076-2 baseline65 K (average)60 K40 °C

Need our certificates?