Quality & approvals
Tested before it leaves.
Certified management systems, routine testing on every unit, and every product mapped to the Indian Standard and its international equivalent.

Routine test panel
Our position
Quality you can trace to a bay.
Owning the process from raw material to tested product means there is no vendor to point at.
Every transformer, conductor and cable is routine-tested before dispatch. Steel is inspected on receipt, coating thickness is checked after galvanizing, and extruded product is monitored continuously for wall thickness and dimension.
Purchasers and third-party agencies may witness testing, including pre-shipment inspection for export.
Standards
What we manufacture against.
Indian Standards and their international equivalents, so a domestic specification translates directly into an export one.
| Product | Indian Standard | International equivalent |
|---|---|---|
| Distribution transformers | IS 1180 (Part 1):2014 Amd. 4 · IS 2026 | IEC 60076 |
| Power transformers | IS 2026 (Parts 1–5) | IEC 60076 |
| Solar / inverter duty transformers | IS 2026 · IS 1180 | IEC 60076 · IEEE C57.110 · C57.159 |
| Servo voltage stabilisers | IS 9815 (Part 1) | — |
| ACSR conductor | IS 398 (Part 2):1996 | IEC 61089 |
| LT & XLPE cable | IS 7098 (Part 1) & (Part 2) | IEC 60502-1 |
| PCC poles | IS 1678:1998 · IS 785:1998 | — |
| Galvanizing | IS 4759:1996 · IS 2629:1985 | ISO 1461:2009 |
| HDPE pipe | IS 4984 | ISO 4427 |
| Drip lateral | IS 13488:2008 · IS 13487 | ISO 9261 |
| Mini sprinkler | IS 14605 | ISO 8026 |
“—”: no international equivalent in common use.
Testing
What happens before dispatch.
Routine testing is built into production, not bolted on at the end of it.
Electrical routine tests
Ratio, polarity, vector group, winding resistance, losses at 50% and 100%, impedance, insulation and dielectric withstand.
Dimensional & electrical
Diameter, lay ratio, resistance, breaking load, insulation resistance and high voltage test.
Coating verification
Coating mass to IS 6745, uniformity to IS 2633 and adhesion to IS 2629 after the zinc bath.
Extrusion control
Continuous wall thickness and outside diameter monitoring, plus hydrostatic pressure testing.





Certifications
Certificates and type tests.
Each certificate is issued against a specific product and rating. Numbers and validity dates are sent with the quotation, or on request.
| Certificate | Scope | Issued by | Number · validity |
|---|---|---|---|
| ISO 9001:2015 | Quality management — manufacturing operations | On enquiry | On enquiry |
| ISO 14001:2015 | Environmental management | On enquiry | On enquiry |
| ISO 45001:2018 | Occupational health and safety | On enquiry | On enquiry |
| BIS licence — IS 1180 (Part 1) | Distribution transformers | Bureau of Indian Standards | CM/L number On enquiry |
| BEE star label | Distribution transformers, star level per model | Bureau of Energy Efficiency | On enquiry |
| Type tests — transformers | Short-circuit, impulse and temperature rise, per rating | CPRI / ERDA | Report numbers On enquiry |
| Type tests — conductor and cable | Mechanical and electrical, per size | NABL-accredited laboratory | Report numbers On enquiry |
| Routine test certificate | Every transformer, conductor and cable before dispatch | Aggarwal Global works | Available on request |
Fields marked On enquiry are issued against a specific enquiry.
For export buyers
IS against IEC
Indian temperature-rise limits are stricter than IEC 60076-2, so a transformer built to IS 1180 meets a tougher thermal standard.
| Class | Winding rise | Top-oil rise | Ambient |
|---|---|---|---|
| Three-phase up to 200 kVA (IS 1180) | 40 K | 35 K | 50 °C |
| Three-phase above 200 up to 2500 kVA (IS 1180) | 45 K | 40 K | 50 °C |
| Single-phase up to 25 kVA (IS 1180) | 40 K | 35 K | 50 °C |
| IEC 60076-2 baseline | 65 K (average) | 60 K | 40 °C |
Need our certificates?
Tell us which product and which certification your project, export consignment or tender requires, and we will send the current documents.