Aggarwal GlobalEmpowering Nation Enquire

1 – 20 MVA

Power Transformers

Power transformers from 1 MVA to 20 MVA in the 33/11 kV class — ONAN, ONAF, ester-filled (KNAN) or dry type (AN), with CRGO or amorphous core, Dyn11 or the vector group your system needs, with on-load or off-circuit tap changing, built to IS 2026 and IEC 60076.

Range1 – 20 MVA
Class33/11 kV
CoolingONAN / ONAF / KNAN / AN
Power transformer under assembly

Power transformer under assembly

01

Overview

7–8 units / month

Fully active and operational power-class output.

1 – 20 MVA

33/11 kV substation and heavy industrial ratings.

ONAN · ONAF · KNAN · AN

Rated output published at each cooling stage.

Power-class capability, in-house.

The power transformer line closed the last gap in the chain. Between distribution and power class we now cover 16 kVA right through to 20 MVA — a span very few regional manufacturers hold on a single site.

The standard substation build is 33/11 kV, Dyn11, ONAN, with an off-circuit tap changer at +5% to −10%. Where the network needs voltage regulation under load we fit an on-load tap changer at +5% to −15%, and where the load profile justifies forced cooling we supply ONAF with a rated output at each cooling stage.

02

Technical data

Specification.

Built to the purchaser's schedule. Fields marked On enquiry are issued against a specific enquiry. Delivery as per the client's requirement, confirmed with the quotation. Open the rows below for construction details, reference tables and fittings.

General

ParameterSpecification
Rated power1 MVA to 20 MVA
Typical ratings1 · 1.6 · 2 · 2.5 · 3.15 · 5 · 6.3 · 8 · 10 · 12.5 · 16 · 20 MVA
Voltage class33 / 11 kV; highest system voltage 36 kV
PhasesThree-phase
TypeOil-immersed, outdoor, core type — plain or corrugated tank; dry type to order
Frequency50 Hz standard; 60 Hz for export
CoolingONAN or ONAF; KNAN / KNAF with natural ester fluid; AN / AF for dry type — rated output stated at each stage
Applicable standardsIS 2026 (Parts 1–5), IS 3639, IEC 60076 series

Electrical

ParameterSpecification
Vector groupDyn11 standard; YNd11, YNyn0, Dd0 and others to order
ImpedancePer rating — see the utility reference table below; tolerance ±10%
Tap changerOff-circuit +5% to −10% in 2.5% steps (7 positions), or on-load +5% to −15% in 1.25% steps (17 positions)
Neutral earthingSolidly earthed; other arrangements to order
Insulation level (BIL)170 kVp at 33 kV; 75 kVp at 11 kV
Temperature rise45 K winding / 40 K top oil over 50 °C ambient, or 55 K / 50 K where the specification allows
Short-circuit withstandPer IS 2026 (Part 5) — 2 seconds at the specified fault level
Guaranteed lossesAs per technical specification — no-load and load losses guaranteed per rating against the purchaser's schedule
Construction and further particularsMaterials, tank, paint and mechanical details

Construction

ParameterSpecification
CoreCRGO silicon steel lamination to IS 3024, step-lap mitred, bolt-free clamping; amorphous metal core where the loss schedule calls for it
WindingsElectrolytic copper, disc or helical by rating
Insulating fluidMineral transformer oil to IS 335:2018, or natural ester (K-class) fluid to IEC 62770
Oil preservationConservator with diaphragm sealing, at least 10% of total oil volume
RadiatorsDetachable pressed-steel radiators with shut-off valves, air release and drain plug
TankFabricated plain or corrugated, vacuum and pressure tested
PaintingFour coats, 52–60 µm total dry film, shade 632 Admiral Grey per IS 5
Marshalling boxIP55, weather and vermin proof, with space heater and MCB
Reference data — what the standards requireTables from the Indian Standard, for checking any quotation against it

Impedance as specified by Indian utilities

33/11 kV power transformer impedance — values taken from published Indian utility specifications
RatingImpedance at 75 °C, principal tapSpecified by
3.15 MVA6.25%OPTCL
5.0 MVA7.15%OPTCL, APDCL, MSEDCL
8.0 MVA8.35%OPTCL
10.0 MVA8.35%APDCL, MSEDCL

Reproduced so you can see the basis we work to. Your own specification governs; we build to it.

Tapping ranges — IS 1180 (Part 1) and Indian utility practice
ClassTap positionsRange
Three-phase up to 200 kVA4+2.5% to −5% of HV in 2.5% steps
Three-phase above 200 up to 2500 kVA7+5% to −10% of HV in 2.5% steps
Power transformer, off-circuit (utility practice)7+5% to −10% in 2.5% steps
Power transformer, on-load (utility practice)17+5% to −15% in 1.25% steps
Temperature rise limits — IS 1180 (Part 1) against IEC 60076-2
ClassWinding rise (by resistance)Top-oil rise (by thermometer)Ambient basis
Three-phase up to 200 kVA (IS 1180)40 K35 K50 °C
Three-phase above 200 up to 2500 kVA (IS 1180)45 K40 K50 °C
Single-phase up to 25 kVA (IS 1180)40 K35 K50 °C
IEC 60076-2 baseline65 K (average)60 K40 °C
Standard and optional fittingsWhat is supplied as standard, and what is available to order

Standard Fittings

Supplied as standard

  • Conservator with diaphragm oil sealing and isolating valves
  • Magnetic oil level gauge, 150 mm dial, with low-level alarm contact
  • Double-float Buchholz relay with isolating valves, bleed valve and test cock
  • Spring-loaded pressure relief device with alarm and trip contacts
  • Oil temperature indicator and winding temperature indicator, 150 mm dials
  • Silica gel breather with oil seal
  • Detachable radiators with top and bottom shut-off valves
  • Two 50 mm filter valves on diagonally opposite corners
  • Bottom drain-cum-sampling valve, padlockable
  • HV and LV bushings with arcing horns and bimetallic connectors
  • Marshalling box to IP55 with space heater
  • Lifting lugs, jacking pads, haulage lugs and bidirectional flanged rollers
  • Rating, diagram, details, guarantee and danger plates

Testing

Routine tests before dispatch

  • Winding resistance at each tap
  • Ratio, polarity and phase relationship
  • Impedance voltage at minimum, normal and maximum tap
  • Load loss and no-load loss at 100% and 110% voltage
  • Insulation resistance and polarisation index
  • Harmonic level in no-load current
  • Separate-source and induced overvoltage withstand
  • OLTC duty cycle through all positions
  • Core insulation test at 2000 V for 1 minute
  • Capacitance and tan delta
  • Tank vacuum test and pressure test
  • Oil leakage and gas collection
03

Compliance

Standards & testing.

Routine tests are performed on every unit before dispatch. Type tests are certified from CPRI, ERDA or NABL-accredited laboratories on request.

Standards we manufacture and test to
StandardScope
IS 1180 (Part 1):2014Outdoor oil-immersed distribution transformers up to 2500 kVA, 33 kV — including the energy-efficiency levels
IS 2026 (Parts 1–5)Power transformers — general, temperature rise, insulation levels, terminal markings, short-circuit withstand
IEC 60076 seriesInternational power transformer standard — the export equivalent
IS 3024Cold-rolled grain-oriented (CRGO) electrical steel sheet and strip
IS 335:2018Insulating mineral oil for transformers and switchgear
IS 3639:1966Fittings and accessories for power transformers
IS 2099 / IS 7421HV and LV porcelain bushings
IS 3637Gas-and-oil-operated (Buchholz) relays
IS 5:2007Colours for ready-mixed paints — shade 631 for distribution, 632 Admiral Grey for power
IS 6600:1978Guide for loading of oil-immersed transformers

Type & special tests

Available on request

  • Lightning impulse with chopped wave, all three phases HV and LV — IS 2026 (Part 3)
  • Temperature-rise test on the extreme minus tap — IS 2026 (Part 2)
  • Thermal and dynamic short-circuit withstand — IS 2026 (Part 5)
  • Noise level measurement — IS 2026 (Part 10)
  • Post-short-circuit reactance change limited to 2%
  • Frequency response analysis (FRA) as a special test
  • Dissolved gas analysis as a special test
Third-party inspection

Purchaser and third-party pre-dispatch inspection is accommodated on request, including for export consignments. Type-test certificates are issued from CPRI, ERDA or NABL-accredited laboratories — copies available on request.

Applications

Where it goes to work.

Substation

Distribution substations

33/11 kV substation duty across utility networks.

Industry

Heavy industrial plant

Process plant, rolling mills and large manufacturing loads.

Infrastructure

Industrial parks

Bulk supply into planned industrial and warehousing estates.

Renewables

Generation evacuation

Step-up duty at solar and wind plants — see our solar transformer page.

FAQ

Questions

Frequently asked.

What is the largest power transformer you manufacture?
20 MVA. From 1 MVA up we cover the full ladder — 1, 1.6, 2, 2.5, 3.15, 5, 6.3, 8, 10, 12.5, 16 and 20 MVA — in the 33/11 kV class.
Do you supply on-load tap changers?
Yes. Off-circuit tapping at +5% to −10% in 2.5% steps is standard for the smaller ratings; on-load tap changers at +5% to −15% in 1.25% steps, 17 positions, are supplied where the network needs regulation under load.
What is the difference between ONAN and ONAF on your units?
ONAN is oil-natural, air-natural — convection cooling through the radiators with no fans. ONAF adds forced-air fans to lift the rated output of the same core and coil assembly, typically by around a third. We publish the rated output at each cooling stage on the rating plate.
Can you meet a DISCOM's guaranteed technical particulars schedule?
Yes. Send the GTP format with your enquiry and we will return it completed for the rating and tap range you need.

Discuss a power transformer requirement.

Send the rating, voltage class, vector group, impedance and tap range you need, and we will confirm feasibility and delivery.