Aggarwal GlobalEmpowering Nation Enquire

16 kVA – 1000 kVA

Distribution Transformers

Oil-immersed, ester-filled and dry type distribution transformers from 16 kVA to 1000 kVA (1 MVA) in the 11 kV and 33 kV classes, with CRGO or amorphous cores — built to IS 1180 and IS 2026, to any energy-efficiency level, and to your vector group and impedance rather than only ours.

Range16 – 1000 kVA
Output900 jobs a month
StandardIS 1180 (Part 1):2014
Finished distribution transformers in the dispatch yard

Finished distribution transformers in the dispatch yard

01

Overview

900 jobs / month

Sustained distribution-class output across the rating range.

16 – 1000 kVA

The full IS 1180 distribution ladder, single and three phase.

Level 1 to Level 5

Built to whichever IS 1180 efficiency level your tender specifies.

Any rating in the distribution class.

Distribution transformers are the highest-volume line on the campus — around 900 jobs a month across the full IS 1180 rating ladder, from 16 kVA agricultural units to 1000 kVA industrial supply.

Standard build is Dyn11, ONAN, 11/0.433 kV or 33/0.433 kV, with off-circuit tapping. But almost nothing here is fixed: vector group, impedance, tapping range, winding material, fittings and efficiency level are all specified by the purchaser, and we build to that schedule rather than asking you to accept ours.

02

Technical data

Specification.

Built to the purchaser's schedule. Fields marked On enquiry are issued against a specific enquiry. Delivery as per the client's requirement, confirmed with the quotation. Open the rows below for construction details, reference tables and fittings.

General

ParameterSpecification
Rated capacity16 kVA to 1000 kVA (1 MVA)
PhasesThree-phase and single-phase
TypeOil-immersed, outdoor — sealed corrugated-tank or conservator type; dry type (AN) for indoor duty
Voltage class11 kV, 22 kV and 33 kV systems
Standard voltage ratios11 / 0.433 kV · 22 / 0.433 kV · 33 / 0.433 kV · 11 / 0.25 kV single-phase
Frequency50 Hz standard; 60 Hz for export
CoolingONAN; ONAF on larger ratings; KNAN with natural ester fluid; AN for dry type
MountingPole, plinth or platform — pole mounting up to 500 kVA by agreement
DutyContinuous, outdoor
Applicable standardsIS 1180 (Part 1), IS 2026 (Parts 1–5), IEC 60076 for export

Electrical

ParameterSpecification
Vector groupDyn11 standard; Dyn1, Dyn5, YNyn0, Yzn11 and others to order
ImpedancePer IS 1180 — 4.50% up to 630 kVA, 5.00% above 630 kVA to 1000 kVA (±10%)
TappingOff-circuit tap changer, +5% to −10% in 2.5% steps (7 positions); ranges to order
Energy efficiencyIS 1180 Level 1 to Level 5 — specify the level required
No-load current≤ 3% of full-load current up to 200 kVA; ≤ 2% above 200 kVA
Insulation level (BIL)75 kVp at 11 kV; 125 kVp at 22 kV; 170 kVp at 33 kV
Temperature rise45 K winding by resistance, 40 K top oil, over 50 °C ambient
Insulation classClass A
Guaranteed lossesAs per technical specification — no-load and load losses guaranteed per rating against the purchaser's schedule
Construction and further particularsMaterials, tank, paint and mechanical details

Construction

ParameterSpecification
CoreCRGO silicon steel lamination to IS 3024, step-lap mitred, or amorphous metal core for the lowest no-load loss
WindingsCopper or aluminium — specify; layer or helical construction by rating
Insulating fluidMineral transformer oil to IS 335:2018, or natural ester (K-class) fluid to IEC 62770; none in dry type units
TankFabricated plain or corrugated; corrugation minimum 1.0 mm per IS 1180
Surface preparationShot blasted to Sa 2½ (ISO 8501-1)
PaintingInterior hot-oil-resistant ≥ 35 µm; exterior powder or epoxy-PU, shade 631 per IS 5
Mounting channelsMinimum 75 × 40 mm up to 200 kVA
Pressure test100 kPa plain tanks; 15 kPa corrugated tanks per Amendment 4
Reference data — what the standards requireTables from the Indian Standard, for checking any quotation against it

Standard ratings and impedance

Preferred ratings — IS 1180 (Part 1) Table 1
Nominal system voltageStandard ratings (kVA)
Up to and including 11 kV6.3*, 10, 16, 20*, 25, 40*, 63, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000
Above 11 kV up to 22 kV63, 100, 160, 200, 250, 315, 400, 500, 630, 800, 1000
Above 22 kV up to 33 kV100, 160, 200, 250, 315, 400, 500, 630, 800, 1000

* Non-preferred rating. Amendment 4 (2021) extends the small-rating list to all voltage classes.

Short-circuit impedance — IS 1180 (Part 1) Tables 3, 6 and 9
Rating bandPercentage impedance
16 – 630 kVA, three-phase4.50%
800, 1000 kVA, three-phase5.00%
5 kVA, single-phase2.50%
10 – 100 kVA, single-phase4.00%

Tolerance ±10% per IS 2026. Most DISCOM specifications write this as “±10%, no negative tolerance”.

Energy efficiency levels

IS 1180 does not cap no-load and load loss separately. It caps total loss at 50% and at 100% load, and lets the designer trade one against the other. Amendment 4 of March 2021 deleted the loosest level and added two tighter ones, so there are now five levels — a great deal of material still in circulation quotes the old three-level numbering, under which today's Level 1 was called Level 2.

Maximum total losses, three-phase up to 200 kVA, 11 kV class — IS 1180 (Part 1) Amendment 4:2021
kVA%ZLevel 1
50% / 100%
Level 2
50% / 100%
Level 3
50% / 100%
Level 4
50% / 100%
Level 5
50% / 100%
164.5135 / 440120 / 400108 / 36497 / 33187 / 301
254.5190 / 635175 / 595158 / 541142 / 493128 / 448
634.5340 / 1140300 / 1050270 / 956243 / 870219 / 791
1004.5475 / 1650435 / 1500392 / 1365352 / 1242317 / 1130
1604.5670 / 1950570 / 1700513 / 1547462 / 1408416 / 1281
2004.5780 / 2300670 / 2100603 / 1911543 / 1739488 / 1582

Watts. Both caps must be met: total loss at 50% load and at 100% load. The 50% figure is usually the binding one, and it is what drives low no-load-loss design.

Maximum total losses, three-phase 250 to 1000 kVA, 11 kV class — IS 1180 (Part 1) Amendment 4:2021
kVA%ZLevel 1
50% / 100%
Level 2
50% / 100%
Level 3
50% / 100%
Level 4
50% / 100%
Level 5
50% / 100%
2504.50980 / 2930920 / 2700864 / 2488811 / 2293761 / 2113
3154.501025 / 3100955 / 2750890 / 2440829 / 2164772 / 1920
4004.501225 / 34501150 / 33301080 / 32141013 / 3102951 / 2994
5004.501510 / 43001430 / 41001354 / 39091282 / 37271215 / 3554
6304.501860 / 53001745 / 48501637 / 44381536 / 40611441 / 3717
8005.002287 / 64032147 / 58382015 / 53231892 / 48531776 / 4425
10005.002790 / 77002620 / 70002460 / 63642310 / 57852170 / 5259

Above 11 kV up to 22 kV, permitted losses are 5% higher; above 22 kV up to 33 kV, 7.5% higher. IS 1180 allows no positive tolerance on maximum total losses.

Insulation, temperature rise and tapping

Insulation levels — IS 1180 (Part 1)
Nominal system voltageImpulse withstand (kVp)Power-frequency withstand (kV rms)
3.3 kV40—
6.6 kV60—
11 kV7528
22 kV12550
33 kV17070
Temperature rise limits — IS 1180 (Part 1) against IEC 60076-2
ClassWinding rise (by resistance)Top-oil rise (by thermometer)Ambient basis
Three-phase up to 200 kVA (IS 1180)40 K35 K50 °C
Three-phase above 200 up to 2500 kVA (IS 1180)45 K40 K50 °C
Single-phase up to 25 kVA (IS 1180)40 K35 K50 °C
IEC 60076-2 baseline65 K (average)60 K40 °C

Indian limits are materially stricter than the IEC baseline. Export buyers reading IEC numbers will not otherwise realise this.

Tapping ranges — IS 1180 (Part 1) and Indian utility practice
ClassTap positionsRange
Three-phase up to 200 kVA4+2.5% to −5% of HV in 2.5% steps
Three-phase above 200 up to 2500 kVA7+5% to −10% of HV in 2.5% steps
Power transformer, off-circuit (utility practice)7+5% to −10% in 2.5% steps
Power transformer, on-load (utility practice)17+5% to −15% in 1.25% steps
Standard and optional fittingsWhat is supplied as standard, and what is available to order

Standard Fittings

Supplied as standard

  • Two earthing terminals with earthing symbol
  • Rating plate and terminal marking plate
  • Oil level gauge marked minimum / 30 °C / maximum
  • Air release device and silica-gel dehydrating breather
  • Drain-cum-sampling valve — three-phase above 500 kVA
  • Thermometer pocket with cap
  • Lifting lugs for the complete unit and for the core-and-winding assembly
  • Pressure relief device — all sealed types, and above 200 kVA
  • Filter valve on the upper side above 200 kVA
  • HV neutral grounding strip and arcing horns on the HT side
  • Buchholz relay above 1000 kVA

Optional Fittings

Available to order

  • Enhanced dehydrating breather on ratings up to 200 kVA
  • Lightning arrestors and bird guards
  • Bimetallic terminal connectors to IS 5561
  • Oil and winding temperature indicators above 200 kVA
  • Magnetic oil level gauge and jacking pads above 1600 kVA
  • Buchholz relay as an option above 200 kVA
  • Non-return valve and protection relay on sealed units
  • Anti-theft fasteners and locking caps on valves
  • Unidirectional rollers above 200 kVA
  • LV cable box with MCCB or distribution board
  • Conservator with drain plug
03

Compliance

Standards & testing.

Routine tests are performed on every unit before dispatch. Type tests are certified from CPRI, ERDA or NABL-accredited laboratories on request.

Standards we manufacture and test to
StandardScope
IS 1180 (Part 1):2014Outdoor oil-immersed distribution transformers up to 2500 kVA, 33 kV — including the energy-efficiency levels
IS 2026 (Parts 1–5)Power transformers — general, temperature rise, insulation levels, terminal markings, short-circuit withstand
IEC 60076 seriesInternational power transformer standard — the export equivalent
IS 3024Cold-rolled grain-oriented (CRGO) electrical steel sheet and strip
IS 335:2018Insulating mineral oil for transformers and switchgear
IS 3639:1966Fittings and accessories for power transformers
IS 2099 / IS 7421HV and LV porcelain bushings
IS 3637Gas-and-oil-operated (Buchholz) relays
IS 5:2007Colours for ready-mixed paints — shade 631 for distribution, 632 Admiral Grey for power
IS 6600:1978Guide for loading of oil-immersed transformers
Routine and type testsPerformed on every unit, and available on request

Routine tests

Performed on every unit

  • Winding resistance at each tap — IS 2026 (Part 1) cl. 16.2
  • Voltage ratio, polarity, phase sequence and vector group — cl. 16.3
  • Short-circuit impedance and load loss at 50% and 100% — cl. 16.4
  • No-load loss and no-load current at 90%, 100% and 112.5% voltage — cl. 16.5
  • Insulation resistance — cl. 16.6
  • Separate-source voltage withstand — IS 2026 (Part 3) cl. 10
  • Induced overvoltage withstand — IS 2026 (Part 3) cl. 11
  • Pressure test — IS 1180 (Part 1) cl. 21.5.1.2
  • Oil leakage test — IS 1180 (Part 1) cl. 21.5.1.3
  • Oil breakdown voltage and moisture content — IS 335:2018

Type & special tests

Available on request

  • Lightning impulse test — IS 2026 (Part 3) cl. 12
  • Temperature-rise test — IS 2026 (Part 2) cl. 4
  • Short-circuit withstand — IS 2026 (Part 5)
  • Sound level determination — IS 2026 (Part 10)
  • Paint adhesion, cross-hatch — ASTM D3359
  • Magnetic balance test, HV and LV — CBIP Publication 317
  • IP55 verification of cable box — IS/IEC 60529
Third-party inspection

Purchaser and third-party pre-dispatch inspection is accommodated on request, including for export consignments. Type-test certificates are issued from CPRI, ERDA or NABL-accredited laboratories — copies available on request.

Applications

Where it goes to work.

Utility

Distribution networks

Rural and urban feeders under national electrification and distribution strengthening programmes.

Agriculture

Agricultural feeders

Pump-set and tube-well supply, including separated agricultural feeder schemes.

Industry

Industrial supply

Plant, warehousing and industrial estate supply at the higher end of the rating range.

Commercial

Developments

Township, institutional and commercial complex distribution.

FAQ

Questions

Frequently asked.

What is the smallest and largest distribution transformer you manufacture?
16 kVA to 1000 kVA (1 MVA). Above 1 MVA the unit moves into the power-transformer class, which we build up to 20 MVA.
Which vector group do you supply?
Dyn11 is standard and is what IS 1180 mandates for three-phase distribution transformers. Dyn1, Dyn5, YNyn0 and Yzn11 are available to order, as are other groups where the application calls for them.
Can you meet a specific IS 1180 energy efficiency level?
Yes. Tell us the level your tender specifies — Level 1 through Level 5 under the current Amendment 4 numbering — and we design the core and windings to meet both the 50% and 100% total-loss caps. Note that a great deal of older material still uses the pre-2021 three-level numbering.
Do you supply copper or aluminium windings?
Both. Copper is the default where a tender specifies it or where load losses are being penalised heavily; aluminium is offered where the specification permits it. State which you require with your enquiry.

Send us your transformer schedule.

Share the ratings, voltage class, vector group, impedance, loss level and quantity required, and we will return a quotation with a firm delivery programme.