Solar & Inverter Duty Transformers in Jammu and Kashmir
Up to 20 MVA. Delivery across Jammu and Kashmir about 3 days by road, built to the specification your utility or project issues.

Tanks awaiting core-and-coil assembly
Logistics and network
Supplying Jammu and Kashmir.
Deliveries across Jammu and Kashmir start at about 500 km by road, which puts the nearer cities (Kathua, Jammu, Srinagar) within 3 days of dispatch. The state's demand centres on Jammu Bari Brahmana and Samba industrial estates, Srinagar, Kathua, hydro projects.
Distribution in Jammu and Kashmir is handled by JPDCL and KPDCL; JKPTCL runs the transmission network. Programmes now in execution include RDSS, J&K distribution strengthening, and each is tendered against a technical specification that we quote and manufacture to.
The product
A solar transformer is not a distribution transformer with a different label.
An inverter feeds the transformer a non-sinusoidal current with significant harmonic content, and it does so on a duty cycle that is de-energised for roughly half the year. Both facts change the design.
Harmonic currents drive eddy-current heating in the windings that a standard design does not allow for, so conductors are transposed and the core flux density is de-rated to leave headroom. The overnight de-energised period means no-load loss dominates lifetime energy cost far more than it does on a distribution feeder — which is why the low-no-load-loss design is worth paying for here and not always elsewhere.
| Parameter | Specification |
|---|---|
| Rated power | Up to 20 MVA |
| HV voltage | 11 kV or 33 kV |
| LV voltage | 315 / 380 / 415 / 480 / 600 / 690 / 800 V — the inverter output, not 433 V |
| Winding arrangement | Two, three or more secondaries; dual secondary is the norm |
| Duty | Step-up, outdoor, solar or wind generation |
| Frequency | 50 Hz standard; 60 Hz for export |
Specifying
What changes for Jammu and Kashmir.
- Design ambient 45 °C Jammu, 35 °C Kashmir; seismic classification Zone V for structures and foundations.
- Inland exposure: standard epoxy-polyurethane exterior finish and hot-dip galvanized steel parts.
- Temperature rise 45 K winding and 40 K top oil over the stated ambient, or 55 K / 50 K where JPDCL and KPDCL specifications allow; losses, impedance and tapping to the utility schedule or IS 1180 level.
Questions
Frequently asked.
How long does delivery of Solar & Inverter Duty Transformers to Jammu and Kashmir take?
Can you build to the JPDCL and KPDCL specification?
Do you supply private buyers and contractors across Jammu and Kashmir, not only utilities?
Send us your Solar & Inverter Duty Transformers schedule for Jammu and Kashmir.
Ratings, quantities, the specification you are buying against and the delivery point. We return a quotation with a firm delivery programme.