16 kVA – 1000 kVA. Manufactured in India to IS and IEC standards and shipped to Sri Lanka: Ex Factory or FOB Mundra / Nhava Sheva.

Finished distribution transformers in the dispatch yard
Logistics and network
Shipping to Sri Lanka.
Consignments for Sri Lanka move Sea from Nhava Sheva or Mundra to Colombo, then road. Typical transit is 4 to 7 days; discharge at Colombo. We quote Ex Factory or FOB Mundra / Nhava Sheva, with payment by LC at sight or advance, USD.
The grid runs at 50 Hz with 400/230 V low-voltage supply and 11 kV and 33 kV distribution; 132 kV and 220 kV transmission. Distribution is operated by Ceylon Electricity Board (CEB) and Lanka Electricity Company (LECO), regulated by Public Utilities Commission of Sri Lanka (PUCSL). Import conformity: SLSI consignment-based import inspection scheme for regulated products including cables and conductors; CEB and LECO technical specifications and type approvals.
Distribution transformers are the highest-volume line on the campus — around 900 jobs a month across the full IS 1180 rating ladder, from 16 kVA agricultural units to 1000 kVA industrial supply.
Standard build is Dyn11, ONAN, 11/0.433 kV or 33/0.433 kV, with off-circuit tapping. But almost nothing here is fixed: vector group, impedance, tapping range, winding material, fittings and efficiency level are all specified by the purchaser, and we build to that schedule rather than asking you to accept ours.
| Parameter | Specification |
|---|---|
| Rated capacity | 16 kVA to 1000 kVA (1 MVA) |
| Phases | Three-phase and single-phase |
| Type | Oil-immersed, outdoor — sealed corrugated-tank or conservator type; dry type (AN) for indoor duty |
| Voltage class | 11 kV, 22 kV and 33 kV systems |
| Standard voltage ratios | 11 / 0.433 kV · 22 / 0.433 kV · 33 / 0.433 kV · 11 / 0.25 kV single-phase |
| Frequency | 50 Hz standard; 60 Hz for export |
Specifying
What changes for Sri Lanka.
- Climate and site: Coastal humid, 35 °C with salt-laden air; hill country above 1,000 m.
- Built to IEC 60076 for 50 Hz, with insulation levels for the 11 kV and 33 kV distribution and 400/230 V secondaries; temperature-rise limits and cooling sized for the stated ambient and altitude.
- Fittings, bushings and tap-changer ranges follow the utility specification (Ceylon Electricity Board (CEB) and Lanka Electricity Company (LECO)); type-test certificates from CPRI or ERDA accompany the offer.
- Documentation: commercial invoice, packing list, certificate of origin, test certificates and the import conformity certificate where Sri Lanka requires one.
Questions
Frequently asked.
How long does delivery of Distribution Transformers to Sri Lanka take?
What documents and certificates come with a consignment to Sri Lanka?
Which standard and voltage class do you build to for Sri Lanka?
Send us your Distribution Transformers schedule for Sri Lanka.
Ratings, quantities, the specification you are buying against and the delivery point. We return a quotation with a firm delivery programme.