Supply · Madhya Pradesh
Distribution Transformers in Madhya Pradesh
16 kVA – 1000 kVA. Delivery across Madhya Pradesh about 3 days by road, built to the specification your utility or project issues.

Finished distribution transformers in the dispatch yard
Logistics and network
Supplying Madhya Pradesh.
Deliveries across Madhya Pradesh start at about 440 km by road, which puts the nearer cities (Gwalior, Sagar, Ujjain) within 3 days of dispatch. The state's demand centres on Indore and Pithampur auto and pharma, Bhopal and Mandideep engineering, Jabalpur defence, Rewa and Omkareshwar solar, Singrauli power, Satna cement.
Distribution in Madhya Pradesh is handled by MPPKVVCL East, Central and West; MPPTCL runs the transmission network. Programmes now in execution include RDSS, Rewa ultra mega solar, Omkareshwar floating solar, and each is tendered against a technical specification that we quote and manufacture to.
Distribution transformers are the highest-volume line on the campus — around 900 jobs a month across the full IS 1180 rating ladder, from 16 kVA agricultural units to 1000 kVA industrial supply.
Standard build is Dyn11, ONAN, 11/0.433 kV or 33/0.433 kV, with off-circuit tapping. But almost nothing here is fixed: vector group, impedance, tapping range, winding material, fittings and efficiency level are all specified by the purchaser, and we build to that schedule rather than asking you to accept ours.
| Parameter | Specification |
|---|---|
| Rated capacity | 16 kVA to 1000 kVA (1 MVA) |
| Phases | Three-phase and single-phase |
| Type | Oil-immersed, outdoor — sealed corrugated-tank or conservator type; dry type (AN) for indoor duty |
| Voltage class | 11 kV, 22 kV and 33 kV systems |
| Standard voltage ratios | 11 / 0.433 kV · 22 / 0.433 kV · 33 / 0.433 kV · 11 / 0.25 kV single-phase |
| Frequency | 50 Hz standard; 60 Hz for export |
Specifying
What changes for Madhya Pradesh.
- Design ambient 50 °C; seismic classification Zone III for structures and foundations.
- Inland exposure: standard epoxy-polyurethane exterior finish and hot-dip galvanized steel parts.
- Temperature rise 45 K winding and 40 K top oil over the stated ambient, or 55 K / 50 K where MPPKVVCL East specifications allow; losses, impedance and tapping to the utility schedule or IS 1180 level.
Questions
Frequently asked.
How long does delivery of Distribution Transformers to Madhya Pradesh take?
Can you build to the MPPKVVCL East specification?
Do you supply private buyers and contractors across Madhya Pradesh, not only utilities?
Send us your Distribution Transformers schedule for Madhya Pradesh.
Ratings, quantities, the specification you are buying against and the delivery point. We return a quotation with a firm delivery programme.