Aggarwal GlobalEmpowering Nation Enquire

Supply · Rwanda

Distribution Transformers in Rwanda

16 kVA – 1000 kVA. Manufactured in India to IS and IEC standards and shipped to Rwanda: Ex Factory or FOB Mundra / Nhava Sheva; CIF Dar es Salaam on request.

Range16 kVA – 1000 kVA
Delivery12 to 16 days to port, 7 to 10 days road
StandardIS 1180 (Part 1):2014
Finished distribution transformers in the dispatch yard

Finished distribution transformers in the dispatch yard

01

Logistics and network

Shipping to Rwanda.

Consignments for Rwanda move Sea to Dar es Salaam, then road on the Central Corridor to Kigali, about 1,400 km; or via Mombasa on the Northern Corridor. Typical transit is 12 to 16 days to port, 7 to 10 days road; discharge at Dar es Salaam or Mombasa, then road. We quote Ex Factory or FOB Mundra / Nhava Sheva; CIF Dar es Salaam on request, with payment by LC at sight or advance, USD.

The grid runs at 50 Hz with 400/230 V low-voltage supply and 30 kV distribution as the national standard, with 15 kV in Kigali and Rwamagana; 110 kV and 220 kV transmission. Distribution is operated by Rwanda Energy Group: Energy Utility Corporation (EUCL) and Energy Development Corporation (EDCL), regulated by Rwanda Utilities Regulatory Authority (RURA). Import conformity: Rwanda Standards Board (RSB) import conformity and REG reticulation standards; IEC designs.

02

The product

Any rating in the distribution class.

Full specification and gallery

Distribution transformers are the highest-volume line on the campus — around 900 jobs a month across the full IS 1180 rating ladder, from 16 kVA agricultural units to 1000 kVA industrial supply.

Standard build is Dyn11, ONAN, 11/0.433 kV or 33/0.433 kV, with off-circuit tapping. But almost nothing here is fixed: vector group, impedance, tapping range, winding material, fittings and efficiency level are all specified by the purchaser, and we build to that schedule rather than asking you to accept ours.

ParameterSpecification
Rated capacity16 kVA to 1000 kVA (1 MVA)
PhasesThree-phase and single-phase
TypeOil-immersed, outdoor — sealed corrugated-tank or conservator type; dry type (AN) for indoor duty
Voltage class11 kV, 22 kV and 33 kV systems
Standard voltage ratios11 / 0.433 kV · 22 / 0.433 kV · 33 / 0.433 kV · 11 / 0.25 kV single-phase
Frequency50 Hz standard; 60 Hz for export
03

Specifying

What changes for Rwanda.

  • Climate and site: Highland, 1,500 to 2,000 m, 28 °C; altitude derating applies.
  • Built to IEC 60076 for 50 Hz, with insulation levels for the 30 kV distribution as the national standard, with 15 kV in Kigali and Rwamagana and 400/230 V secondaries; temperature-rise limits and cooling sized for the stated ambient and altitude.
  • Fittings, bushings and tap-changer ranges follow the utility specification (Rwanda Energy Group: Energy Utility Corporation (EUCL) and Energy Development Corporation (EDCL)); type-test certificates from CPRI or ERDA accompany the offer.
  • Documentation: commercial invoice, packing list, certificate of origin, test certificates and the import conformity certificate where Rwanda requires one.
FAQ

Questions

Frequently asked.

How long does delivery of Distribution Transformers to Rwanda take?
Manufacturing time depends on the rating and quantity and is confirmed with the quotation; shipping is 12 to 16 days to port, 7 to 10 days road via Dar es Salaam or Mombasa, then road. Inspection before dispatch can be arranged for your representative or a third-party agency.
What documents and certificates come with a consignment to Rwanda?
Commercial invoice, packing list, certificate of origin, routine test certificates per unit or drum, and the import conformity paperwork: Rwanda Standards Board (RSB) import conformity and REG reticulation standards; IEC designs.
Which standard and voltage class do you build to for Rwanda?
IEC 60076 and related IEC standards for 50 Hz, with 30 kV distribution as the national standard, with 15 kV in Kigali and Rwamagana, or the Rwanda Energy Group: Energy Utility Corporation (EUCL) and Energy Development Corporation (EDCL) specification where one is issued. Indian Standard designs with IEC equivalents are also accepted on many schemes.

Send us your Distribution Transformers schedule for Rwanda.

Ratings, quantities, the specification you are buying against and the delivery point. We return a quotation with a firm delivery programme.